HVAC Hydronic System with Split Buffer Tank for Zero-Mixing System Operation
The present invention relates to HVAC-systems operating under new ZERO-MIXING (ZM) water flow condition as innovative way to promote consistent highly energy efficient performance on SOURCE-heating/cooling thermal production and BUILDING's system distribution (FIG. 1). ZM technology is applicable; but not limited, to large-residential, commercial, institutional, and industrial facilities. Current state on HVAC technology, for system hydronics loop-flow, do not provide flows temperature segregation mechanisms between heating/chiller-plants hot/cold water supply and warmer water system returns. The result, a system that continuously operates at WATER MIXING conditions that impair equipment efficiency and output, and therefore, overall system energy performance.
This application claims foreign priority benefit under 35 U.S.C. 119(a) of Canadian Patent Application 3,107,539, filed Jan. 29, 2021, the entirety of which is incorporated herein by reference.
FIELD OF INVENTIONThe present invention relates generally to heating and cooling systems, and more particularly to hydronics for heating, cooling and ventilation (HVAC) systems that use a water-based working fluid to fulfill heating/cooling loads of a building and/or heating/cooling needs of an industrial process.
BACKGROUND OF THE INVENTIONDespite technology advancements in heat-power/cooling generation and distribution modern building's HVAC equipment rarely achieve lab-test high efficiencies during actual lifetime operation. As a result, even the most renowned LEED1/ZCB2-certified buildings barely hit the 70% Annual Fuel Utilization Efficiency (AFUE3) mark. Today, modern cities' infrastructure, regardless of retrofit-upgrade opportunities, continue running under an inefficient and ineffective HVAC platform that allows for unnecessary spending of non-renewables and greater production of GHG emissions. 1 Leadership in Energy and Environmental Design.2 Zero Carbon Building Standards.3 Annual Fuel Utilization Efficiency. In short, the AFUE indicates, for each dollar spend on energy for heating by gas, oil, or another fuel, just how much of it shows up inside the occupied space of the building as heat.
As architects and HVAC engineers remain challenged by the existing gap between building design and actual energy performance many professional associations for science and technology, seeking to advance heating, ventilation, air conditioning and refrigeration systems design and construction, continue prototyping and experimenting with new resources to better understand system behaviour.
There is today a continuous struggle to develop the ultimate system that can effectively integrate energy-production with system-distribution, that can also perform at maximum capacity while excelling at part-loads. Yet, under existing design practices and the current state of technology for equipment connectivity (hydronics), favoring system WATER-MIXING conditions, a technological leap to close the gap is needed.
This is the case for building HVAC systems running with condensing boilers with lab-reported high efficiency ratings C≈98%) that once integrated into the system are forced by hydronics to take a life of their own with unexpected consequence on overall system performance. Before sold in the North American market highly efficient condensing boilers are tested and certified under ANSI4/AHRI5 standards. ANSI Steady State Efficiency Test (SSET) simulates artificial conditions by regulating parameters such as fuel, air-intake temperature/volume, air/gas mixture, water/brine temperatures, boiler entering flow, etc., all fixed during boiler firing to ensure that boiler efficiency performance is rated at steady state regime (
Complications during design phase confront engineers with issues arising from differing boiler and building heating operating conditions. There are system conditions which arise from optimal performance of the heating system's terminal units, and there are system conditions which are optimal for efficient boiler plant performance. These two sets of conditions are rarely, and perhaps only accidentally, the same. What is optimal for the former is usually not optimal for the latter, and vice versa. Attempts by designers to accommodate the needs of the boiler when designing system can, and often do, compromise the performance of their systems. Ignoring the needs of the boiler creates short-cycling6, and the energy lost from it often serves to undo the gains made by state-of-the-art system designs. It is as though there are really two systems being designed, the heating system and the boiler plant, which requirements are always different, usually different enough to make differences irreconcilable. 6 Boiler short-cycling consist of a firing interval, a post-purge, and idle period, a pre-purge, and return to firing. During these events, the boiler may exhaust through the chimney between 3% to 7% its hourly boiler output.
Despite host of information available on the web from boiler factory representatives, engineers, and commissioning agents, recommending practices and discussing design issues, specifying a condensing boiler does not guarantee achieving the expected savings since condensing boilers only operates in the condensing range from time-to-time. Manufacturers and engineering challenges become building owner's problem when they are sold on the idea that installing a condensing boiler will grant the building the opportunity to achieve high operating efficiencies, with highly expected savings, ignoring that WATER-MIXING is the real problem impairing boilers and system performance.
Thermal buffer in
In the case of condensing-boiler heating (SOURCE), hot water BWS is produced and pump into system hydronics/thermal-mass. Warmed water SWR, returning from BUILDING's ancillary MAU/UH/others, encounters with BSW during the reheat exchange process. A major problem with existing commercial systems resides in the fact that hydronics allow loop water to recirculate without any ability to separate/redirect the encountering of flows that have very dissimilar thermal characteristics (BWS-hot or SWR-warmer conditions). The lack of a mechanical barrier to control the encounter of hot and warm flows inside hydronics allows the WATER-MIXING phenomena to happen.
Tmix.=(BSW+SWR)/2@mixing point in FIG. 5.
In a typical system BSW is determined by the Outdoor Control Reset (OCR7) based on outdoor weather conditions, while SWR is determined by building's ancillary design. 7 Theoretically, the purpose of outdoor reset is to reduce energy use and cost without sacrificing comfort. The control system lowers the holler water temperature when the outdoor temperature is warmer and increases it when the outdoor temperature is colder.
As water mixing temperature Tmix. increases, during the reheating process, and circulates back to boilers, boilers condensing capability start diminishing, see
Contrary to ANSI/AHRI-SSET high efficiency test Standard8 for boiler optimal output, set at EWT=26.7° C. and LWT=80° C., with ΔT=LWT−EWT=53.3° C. (see
Laboratory test of Applicant's Split Buffer Tank (SBT) (previously patented examples of which are disclosed in Applicant's Canadian Patent CA2701528 and U.S. Patent U.S. Pat. No. 8,997,511, each of which is incorporated herein by reference in its entirety) proved that, under system WATER-MIXING conditions, increasing BRD beyond 20° C. only exacerbate the system performance problem due to thermal-mass reduction. And, that boiler operation below BRD=20° C. constrains boiler output with no added benefit to system performance either.
On the flip side, as water flow temperature Tmix going into building's FCs increases, from setback lower temperature condition, building's FCs efficiency and heat output ramp-up. FCs max output is reached just and point when boiler(s) is shutoff by system setpoint temperature FCs' heat output Q can be calculated with the use of equation 1 and 2 below. See
Q=U×A×MLTD. (1)
MLTD=(ΔT1−ΔT2)/ln(ΔT1/ΔT2) (2)
-
- Q Rate of heat transfer in the heat exchanger between system water supply and building room-air.
- U Overall heat transfer coefficient,
- A Heat transfer surface area in the heat exchanger,
- MLTD is the log mean temperature difference, calculated from the inlet and outlet temperatures of both fluids for room-air entering/leaving temperature and water entering (Tmix.)/leaving water temperature. See
FIG. 6 . - ΔT Entering/leaving temperature differential between the two flows (Room air/water supply).
- ΔT1 twin−taout=Tmix.−taout.
- twin Fan-Coil Water Supply Temperature. Rising with Tmix.
- twout Fan-Coil Water Return Temperature. Leaving heat exchanger—going back to boilers for reheating.
- tain Fan-Coil Air Entering Temperature. From conditioned space.
- Taout Fan-Coil Air Leaving Temperature. To conditioned space.
Equation-2 temperature differentials between hot-water supply and warmer-air stream ΔT1 and ΔT2 determines the output for the FCs' heat-exchanger and therefore the efficiency of the equipment. Since system WATER-MIXING is continuously diluting the thermal-mass temperature Tmix, in an up-and-down fashion, it forces FCs output to fluctuate from optimal design point, forcing secondary-system pumps and fans to work for longer period of time at partial loads. This, causing higher electricity bills and greater equipment wear and tear.
System WATER-MIXING, resulting from hydronics evils, is the worst enemy to overall HVAC system performance. Constant changing Tmix affects the system in many ways, including:
-
- Overall HVAC-system inefficient equipment operation,
- Overall HVAC-system reduced equipment output operation,
- Heating/Cooling plant cycling (temperature controlling),
- Heating/Cooling plant—building system water supply/return looping upset,
- Heating/Cooling plant, building ancillary equipment oversize design.
WATER-MIXING damaging conditions are present in every HVAC application, also including air/ground heat-pumps, solar-thermal, hot-water production (DHW), chilled water, Combined Heat and Power (CHP), and other industrial processes, involving fluid reheating and cooling. It affects overall system efficiency and equipment output in the same manner.
Applicant has invented novel hydronic HVAC systems addressing such shortcomings of conventional hydronic HVAC design.
SUMMARY OF THE INVENTIONAccording to one aspect of the invention, there is provided a hydronic HVAC system comprising:
-
- a heating/cooling source for heating or cooling a working fluid;
- a split-buffer tank comprising a vessel in which there is contained a separation disk that divides an interior space of the vessel into separate supply and return chambers on opposing sides of said separation disk for respective holding of differently temperatured volumes of the working fluid in isolated fashion from another within said separate supply and return chambers, said separation disk being freely movable back and forth in an axial direction of the vessel to vary the relative sizes of said supply and return chambers and thereby accommodate volumetric variation between said differently temperatured volumes of the working fluid;
- a primary fluid loop and a primary pumping system installed therein in a manner operable to pump the working fluid through the heating/cooling source from the return chamber of the split buffer tank to the supply chamber of the split buffer tank;
- a secondary fluid loop and a secondary pumping system installed therein in a manner operable to pump the working fluid from the supply chamber of the split buffer tank to at least one heating/cooling unit that uses the working fluid for heating/cooling purposes, said secondary fluid loop comprising at least one return line through which the working fluid is returnable from at least one heat/cooling unit to the return chamber of the split buffer tank;
- at least one control valve installed in said at least one return line, said at least one control valve being settable into a plurality of different operating states, including at least a recirculation state operable to recirculate said working fluid back through said secondary fluid loop, and a bypass state operable to return said working fluid back to the return chamber of the split buffer tank; and
- a control system configured to operate the secondary pumping system, thereby causing circulation of the working fluid through the secondary fluid loop, and during said circulation of the working fluid through the secondary fluid loop, operate the at least one control valve by performing at least the following steps on an ongoing basis:
- (a) monitoring a fluid return temperature of the working fluid in said at least one return line;
- (b) determine whether the fluid return temperature fulfills a targeted minimum temperature differential relative to an output temperature setpoint of the heating/cooling source to achieve operating efficiency thereof in an optimal range;
- (c) when the return temperature of the working fluid fulfills said targeted minimum temperature differential, set or maintain said at least one control valve in the bypass state; and
- (d) when the return temperature of the working fluid does not fulfill said targeted minimum temperature differential, set or maintain said at least one control valve in the recirculation state.
According to another aspect of the invention, there is provided a method of controlling hydronic heating or cooling, said method comprising:
-
- having hydronic HVAC system comprising:
- a heating/cooling source for heating or cooling a working fluid;
- a split-buffer tank comprising a vessel (1) in which there is contained a separation disk (2) that divides an interior space of the vessel into separate supply and return chambers on opposing sides of said separation disk for respective holding of differently temperatured volumes of the working fluid in isolated fashion from another within said separate supply and return chambers, said separation disk (2) being freely movable back and forth in an axial direction of the vessel to vary the relative sizes of said supply and return chambers and thereby accommodate volumetric variation between said differently temperatured volumes of the working fluid;
- a primary fluid loop in which the heating/cooling source is fluidly connected between the supply and return chambers of the split buffer to receive said working fluid from the return chamber and heat/cool said working fluid, before loading thereof into the supply chamber of the split buffer;
- a secondary fluid loop in which at least one heating/cooling unit is fluidly connected between the supply and return chambers of the split buffer to receive said working fluid from the supply chamber and use said working fluid to address a heating/cooling load, before returning said working fluid to the return chamber;
- during circulation of the working fluid through the secondary fluid loop, performing the following steps:
- (a) monitoring a fluid return temperature of the working fluid in the secondary fluid loop at a location downstream of the at least one heating/cooling unit and upstream of the return chamber of the split buffer;
- (b) determining whether the fluid return temperature fulfills a targeted minimum temperature differential (ΔT) relative to an output temperature setpoint of the heating/cooling source to achieve operating efficiency thereof in an optimal range;
- (c) when the fluid return temperature fulfills said targeted minimum temperature differential (ΔT), returning the working fluid to the return chamber of the split buffer; and
- (d) when the fluid return temperature does not fulfill said targeted minimum temperature differential (ΔT), recirculating the working fluid back through the secondary loop.
- having hydronic HVAC system comprising:
According to yet another aspect of the invention, there is provided split buffer tank for storing temperature-distinct volumes of working fluid therein as a buffer between primary and secondary fluid loops of a hydronic heating/cooling system, said split buffer tank comprising:
-
- a vessel having first and second ends that are spaced apart from one another in an axial direction of the vessel, and that are situated oppositely of one another across an interior space of the vessel delimited between said first and second ends, and a circumferential wall that spans axially between the first and second ends of the vessel and closes circumferentially around the interior space thereof;
- a separation disk that is contained in said vessel and divides the interior space thereof into separate supply and return chambers on opposing sides of said separation disk for respective holding of differently temperatured volumes of the working fluid in isolated fashion from another within said separate supply and return chambers, said separation disk being movable back and forth in the axial direction of the vessel to vary the relative sizes of said supply and return chambers and thereby accommodate volumetric variation between said differently temperatured volumes of the working fluid;
- a shaft spanning across the interior space of the vessel in the axial direction thereof, said shaft penetrating through the first and second ends of the vessel and also through the separation disk, which is slidably disposed around said shaft for sliding movement back and forth along the shaft;
- a supply chamber inlet installed on the first end of the vessel to receive the working fluid from one or more heating/cooling sources in a primary loop of the hydronic heating/cooling system, said supply chamber inlet opening into the supply chamber of the vessel and also receiving a first end portion of the shaft that penetrates through the first end of the vessel, thereby externally supporting said first end portion of the shaft outside the vessel;
- a return chamber inlet installed on the second end of the vessel to receive the working fluid back from a secondary loop of the hydronic heating/cooling system, said return chamber inlet opening into the return chamber of the vessel and also receiving a second end portion of the shaft that penetrates through the second end of the vessel, thereby externally supporting said second end portion of the shaft outside the vessel;
- a supply chamber outlet on the circumferential wall at a location situated axially near the first end to enable supply of the working fluid from the supply chamber into the secondary loop; and
- a return chamber outlet on the circumferential wall at a location situated axially near the second end to enable output of the working fluid from the return chamber into the primary loop.
Innovative ZM HVAC-system operating configuration in
Contrary to the conventional system in
In a ZERO-MIXING multi-service system (
In the first multi-service example (
In the illustrated example TSP=82° C., and so when sensor T1 reaches setpoint condition T1=82° C., the boiler controller shuts off the boiler(s) while the boiler(s) remain(s) fully loaded with hot water at 82° C. Arrival of the separation disk at the bottom of the tank marks the end of the cycle (100% load). At any given time, if system calls for heat, SWS water is pumped from the top supply chamber SC of the tank and supplied to secondary-loop's FCs via hydronics system. Additional reference may be made to Applicant's aforementioned prior patents for further details on the SBT's sequence of operation). System low temperature water return SWR is then bypassed through CV1 and stored at the bottom of SBT, pushing upward the separation disk. As system SWR flow accumulate at SBT bottom, separation disk is pushed top the top of tank where it is bypass into valve T2, at SWS outlet, and low temperature SWR flow turn-on boilers. Pumps P1/P2/P3 can operate concurrently. System-OCR output may be used to control T2 setpoint or to reduce BWS. Dark grey rectangular area represents the energy accumulated in system thermal-mass during system cycle operation.
The ZERO-MIXING Plant Advantage.
Boilers' output drawbacks are the result of system hydronics favouring WATER-MIXING in the reheating/delivery process and the unavoidable boiler/system-running scheme with BRD=20° C., reducing gradually to zero at BIN 20° C./10° C. To overcome such deficiencies engineers are forced to make uneconomical decisions and overdesign plant-capacity to makeup for the lost of it. As weather conditions improve, system rides down the BWS−SWR curves, with boiler output capacity points AB reducing even lower to A′B′. At BIN 10° C./0° C. Boilers may find themselves running for longer time at intermittent operation (short-cycling).
New ZERO-MIXING HVAC-system (
Qb=4,200×FLOW×(BWS−SWR) (3)
-
- Qb Boiler Output Rate (kWatts)
- FLOW Boiler(s) Flow (m3/sec)
- BWS Boiler Water Supply (° C.)
- SWR Building/System Water return (° C.)
At systems design condition C-33° C. DB,
QM=4,200×FLOW×(20° C.) (WATER-MIXING Operation)
QZ=4,200×FLOW×(44° C.) (ZERO-MIXING operation)
Based on boiler output comparison QM/QZ≈0.5 it can be concluded that, boiler output QM gets reduced by 50% due to mixing operation. As building weather conditions move into milder summer periods QM output reduces progressively, with QM=25% QZ at BIN 10° C./0° C. Boilers continuous run at near 100% capacity, under ZERO-MIXING operation, reduces time operation with longer standby periods at milder weather conditions. Since return water is always maintained below 57.2° C., boiler's performance emulates SSET parametric conditions leading to much higher annual system AFUE values, improving building OPEX from fuel savings, carbon tax levy reduction, maintenance and early replacement cost from continuous wear and tear.
The SBT/Building Thermal-Mass Advantage.
Today, HVAC system are designed for loads that rarely occurred (≈2% of seasonal operation), with boilers spending nearly 7,400 hrs (98%) running at partial loads (between bins 20° C./10° C. to −10° C./−20° C.) to overcome smaller building seasonal heat loses due to milder weather conditions. Since in the absence of thermal buffers or larger boiler's thermal-mass, stored piping water thermal-mass is the last resource for a system starving from heat, remaining heat in hydronics is rapidly withdrawn until water temperature condition falls below the system's control system setpoint “T”, forcing boilers to fire. At milder outdoor temperatures (bin 10° C./0° C., see
Purge Differential-PD=4 Purge (WM)−2 Purge (ZM)=2×5% average heat loss=10%
Purge Differential (PD) dashed-line in
WATER-MIXING/ZERO-MIXING System Purge-Differential can be estimated for some BIN as:
BIN 10° C./0° C. C″′D″′/A″′B″′=5.2 PD 3,215 hr., 36% heating operation.
BIN 0° C./−10° C. C″D″/A″B″=3.5 PD 1,925 hr., 22% heating operation.
BIN −10° C./−20° C. C′D′/A′B′=2.7 PD 685 hr., 8% heating operation.
BIN −20° C./−30° C. 2.2 PD 158 hr., 1.8% heating operation.
BIN −30° C./−40° C. CD/AB=2.0 PD 4 hr., 0.04% heating operation.
Looking at year AFUE analysis for the WATER-MIXING system in
In the Primary-only system in
When compared to ZERO-MIXING system, problem in the Primary-only arises with the system need to maintain minimum flow return to boiler(s)/system. To satisfy building minimum loads, most likely happening at BIN 10° C./0° C., point A′B′ in
Short-cycling is also the result of system oversized heating plant with poor boiler(s) turndown ratio or an erratic multi-boiler system water temperature control system. In any case, either a low-mass system, boiler oversize, or water temperature controlling issues, loses small in size take a huge toll on annual boiler AFUE efficiency due to their reoccurring nature. This is usually neglected when analyzing the gap between building design and actual energy performance. No matter what the case is, short-cycling can be eliminated at once with the integration of the ZERO MIXING concept into any HVAC boiler system.
The Boiler/Building System Low-Flow Advantage.
Current HVAC design fundamentals on condensing boiler-systems (
A WATER-MIXING/ZERO-MIXING flow comparison can be analysed through the formula below for a particular boiler output as:
QZ=QM
4,200×FLOWZ×(44° C.)=4,200×FLOWM×(20° C.)
FLOWZ=50% FLOWM
ZERO-MIXING system high temperature differential operation reduce by 50% pumping and air-handling flows without sacrificing boiler or ancillary equipment output. Savings are not limit to operational costs but also to capital investment for new facilities with reduction of otherwise oversize equipment.
The Boiler/Building System Control Advantage.
There are many ways to control a boiler and the boiler controls can be layered. A boiler's own controls can be set for standalone operation to maintain desired boiler setpoints, and also can be linked to a more complex Direct Digital Control (DDC) system for a multi-boiler multi-stage with more complex controlling operation. Customary use of DDC-OCR controls to manage boiler output, coupled with temperature controlled variable flow pumps to produce low temperature water return for boiler condensing opportunities, always result in water mixing in the common heater (
HVAC ZERO-MIXING systems use SBT as the main point for system-loops coupling/decoupling. SBT on-stream sensing at the inlets/outlets of the tank (TS1/TS2/TS3/TS4,
The SBT on-stream sensing system in
HVAC Cooling Primary-Only System and WATER-MIXING Operation.
Conversion to ZERO-MIXING of a conventional HVAC-Cooling Primary-only system (
In operation, the difference is that the supply chamber SC holds cold water received from the chiller CH, and the return chamber RC holds warmer water received back from the ancillary equipment (e.g. FCs) in the secondary loop responsible for cooling the building. Accordingly, in this cooling application, instead of bypassing the SWR to the SBT when the SWR temperature TSWR is below the CV1 setpoint stored in the PLC, the PLC instead sets CV1 to perform such bypass when TSWR is above the CV1 setpoint. This is because the temperature differential in this cooling system context is one where a large temperature differential requires a higher TSWR value, since SWR is warmer than SWS. Here, compressor runs happen at equipment stationary conditions sustaining equipment max capacity and efficiency. Utilization of SBT thermal-mass also allow system to take advantage of Free-cooling options.
As a novel alternative to either the conventional Primary-secondary loop system in
-
- Maximize overall HVAC-System AFUE,
- Continuous SOURCE max output operation,
- Continuous SOURCE max efficiency operation,
- SOURCE short-cycling elimination,
- System Thermal-mass addition,
- Improved temperature sensing/controlling,
- Improve ancillary equipment operation,
- Seamless coupling/decoupling loops hydronic,
- New approach to system design (50% lower flow operation).
While the HVAC systems disclosed herein may use the SBT disclosed in Applicant's aforementioned prior patents,
A separation disk 2 is contained within the vessel and divides the interior space thereof into separate supply and return chambers (SC, RC) on opposing sides of said separation disk for respective holding the differently temperatured volumes of the working fluid in isolated fashion from another within these chambers. The disk is being movable back and forth (e.g. up and down) in the axial direction of the vessel along a central longitudinal axis thereof. Such disk movement varies the relative sizes of said supply and return chambers and thereby accommodates volumetric variation between the fluid pumped into the supply chamber from the boiler, chiller or other heating/cooling source, and the fluid returned from the secondary loop.
To help guide water-driven movement of the disk 2 and maintain the disk in perpendicular orientation to the vessel axis on which it moves back and forth, a guide shaft 7 spans across the interior space of the vessel on the central longitudinal axis thereof. The shaft penetrates centrally through both ends of the vessel, and also through the separation disk that is slidable back and forth along the shaft. An outer periphery of the disc has a seal that engages the interior surface of the vessel's circumferential wall to maintain a fluid tight, but slidable, relation therewith. This allows movement of the disk, while maintaining fluid isolation between the two chambers of the vessel's interior space to prevent water from leaking across the disk from one chamber to the other.
A supply chamber inlet 5 is installed on the first end of the vessel to receive the working fluid from the one or more heating/cooling sources in the primary loop of the hydronic heating/cooling system. This supply chamber inlet opens into the supply chamber of the vessel, and also receives a first end portion of the shaft that penetrates through the first end of the vessel. The supply chamber inlet 5 thus doubles as an external support for holding the first end portion of the shaft at a position outside the vessel. The fitting installed on the vessel to form this supply chamber inlet 5 thus makes use of a singular hole at a singular location in the vessel walls to both introduce the working fluid to the supply chamber, and support a respective end of the shaft. This also simplifies the tank design by avoiding the need to somehow install shaft-holding components inside the vessel.
Likewise, a return chamber inlet 6 is installed on the second end of the vessel to receive the working fluid back from the secondary loop of the hydronic heating/cooling system. This return chamber inlet opens into the return chamber of the vessel, and also receives a second end portion of the shaft that penetrates through the second end of the vessel. Like the supply chamber inlet, the return chamber inlet 6 thus doubles as an external support for holding the second end portion of the shaft at a position outside the vessel, once again reducing the overall quantity of holes in the tank walls, and simplifying the construction by avoiding internally mounted shaft supports.
Meanwhile, a supply chamber outlet is provided on the circumferential wall at a location situated axially near the first end of the vessel, and enables supply of the working fluid from the supply chamber into the secondary loop to feed the ancillary equipment (e.g. FC1, FC2, FC3, HP, MUA, and/or DHW) installed therein. Similarly, a return chamber outlet is also on the circumferential wall at a location situated axially near the second end of the vessel, and enables output of the working fluid from the return chamber into the primary loop to feed the heating/cooling source (e.g. B-1, B-2, or CH) during operation of the primary loop's pumping system (e.g. P1, P2).
Though the SBT may use the stops and disk bypasses described in Applicant's aforementioned prior patents, the illustrated example lacks such features, and relies on movement of the disk fully past either chamber's outlet to allow water from the other chamber to pass therethrough when that other chamber is filled to its maximum capacity.
While the detailed embodiments above make reference to a PLC or other controller connected to the control valve(s) in the return line(s) of the secondary loop to control operation of these valves based on a control valve setpoint, which may be a floating setpoint that varies with outdoor temperature read by a connected OCR, and use of a separate heating/cooling source controller (e.g. boiler controller) to control operation of the heating/cooling source based on temperature readings from sensors T1, T2 that measure fluid temperature from the supply and return chamber outlets of the SBT, it will be appreciated that these and any other control functions mentioned herein may be consolidated into a singular controller, or distributed among a greater number of discrete controllers, without affecting the overall function of the inventive system. Accordingly, the term control system is used herein to denote any quantity of electronic controllers programmed to carry out any and all operations described herein on an automated basis.
Claims
1. A hydronic HVAC system comprising:
- a heating/cooling source (B1-B2/CH) for heating or cooling a working fluid;
- a split-buffer tank (SBT) comprising a vessel (1) in which there is contained a separation disk (2) that divides an interior space of the vessel into separate supply and return chambers (SC, RC) on opposing sides of said separation disk for respective holding of differently temperatured volumes of the working fluid in isolated fashion from another within said separate supply and return chambers, said separation disk (2) being freely movable back and forth in an axial direction of the vessel to vary the relative sizes of said supply and return chambers and thereby accommodate volumetric variation between said differently temperatured volumes of the working fluid;
- a primary fluid loop and a primary pumping system (P1, P2) installed therein in a manner operable to pump the working fluid through the heating/cooling source from the return chamber of the split buffer tank to the supply chamber of the split buffer tank;
- a secondary fluid loop and a secondary pumping system (P3) installed therein in a manner operable to pump the working fluid from the supply chamber of the split buffer tank to at least one heating/cooling unit (FC1, FC2, FC3, HP, MUA, DHW) that uses the working fluid for heating/cooling purposes, said secondary fluid loop comprising at least one return line through which the working fluid is returnable from at least one heat/cooling unit to the return chamber of the split buffer tank;
- at least one control valve (CV1, CV2, CV3) installed in said at least one return line, said at least one control valve being settable into a plurality of different operating states, including at least a recirculation state operable to recirculate said working fluid back through said secondary fluid loop, and a bypass state operable to return said working fluid back to the return chamber of the split buffer tank; and
- a control system configured to operate the secondary pumping system, thereby causing circulation of the working fluid through the secondary fluid loop, and during said circulation of the working fluid through the secondary fluid loop, operate the at least one control valve by performing at least the following steps on an ongoing basis: (a) monitoring a fluid return temperature (TSWR) of the working fluid in said at least one return line; (b) determine whether the fluid return temperature (ISWR) fulfills a targeted minimum temperature differential (ΔT) relative to an output temperature setpoint (TSP) of the heating/cooling source to achieve operating efficiency thereof in an optimal range; (c) when the return temperature of the working fluid fulfills said targeted minimum temperature differential, set or maintain said at least one control valve in the bypass state; and (d) when the return temperature of the working fluid does not fulfill said targeted minimum temperature differential, set or maintain said at least one control valve in the recirculation state.
2. The system of claim 1 wherein said heat/cooling source is a heating source (B1-B2), step (b) comprises determining whether the fluid return temperature fulfills the targeted temperature differential by checking whether the fluid return temperature is less than a control valve setpoint value, step (c) comprises setting or maintaining said at least one control valve in the bypass state when the fluid return temperature is less than the control valve setpoint value, and step (d) comprises setting or maintaining said at least one control valve in the recirculation state when the fluid return temperature is greater than the control valve setpoint value.
3. The system of claim 1 wherein said heat/cooling source is a cooling source (CH), step (b) comprises determining whether the fluid return temperature fulfills the targeted temperature differential by checking whether the fluid return temperature is greater than a control valve setpoint value, step (c) comprises setting or maintaining said at least one control valve in the bypass state when the fluid return temperature is greater than the control valve setpoint value, and step (d) comprises setting or maintaining said at least one control valve in the recirculation state when the fluid return temperature is less than the control valve setpoint value.
4. The system of any claim 1 wherein the control system is configured to variably adjust the targeted minimum temperature differential.
5. The system of claim 4 wherein the control system is configured to variably adjust the targeted minimum temperature differential based at least partly on an outdoor temperature.
6. The system of claim 2 wherein the control system is configured to variably adjust the control valve setpoint value.
7. The system of claim 6 wherein the control system is configured to variably adjust the control valve setpoint value based at least partly on an outdoor temperature.
8. The system claim 1 wherein the secondary fluid loop comprises a plurality of fluid circuits through which the working fluid is respectively delivered to a plurality of different heating/cooling equipment types (HP, MUA, DHW), the at least one return line comprises a plurality of respective return lines each belonging to a respective one of the fluid circuits, the at least one control valve comprises a plurality of respective control valves (CV1/CV1′, CV2, CV3) each installed in a respective one of said plurality of return lines, and the control system is configured to monitor a respective fluid return temperature in each of said return lines, and to control the respective control valve of each return line based on the respective fluid return temperature in said return line.
9. The system of claim 8 wherein each respective control valve (CV1, CV2, CV3), in the recirculation state thereof, is operable to recirculate the working fluid back through a same one of the fluid circuits in which said respective control valve is installed.
10. The system of claim 8 wherein at least one of the respective control valves (CV1′), in the recirculation state thereof, is operable to recirculate the working fluid through a different one of the fluid circuits that that in which said respective control valve is installed.
11. The system of claim 10 wherein the heating/cooling source is a heating source (B1-B2), and said at least one of the respective control valves is a first control valve (CV1′) installed in the respective return line of a first fluid circuit whose respective fluid return temperature is greater than a second fluid circuit into which the first control valve is operable, in the recirculation state thereof, to recirculate the working fluid.
12. A method of controlling hydronic heating or cooling, said method comprising:
- having hydronic HVAC system comprising: a heating/cooling source (B1-B2/CH) for heating or cooling a working fluid; a split-buffer tank (SBT) comprising a vessel (1) in which there is contained a separation disk (2) that divides an interior space of the vessel into separate supply and return chambers (SC, RC) on opposing sides of said separation disk for respective holding of differently temperatured volumes of the working fluid in isolated fashion from another within said separate supply and return chambers, said separation disk (2) being freely movable back and forth in an axial direction of the vessel to vary the relative sizes of said supply and return chambers and thereby accommodate volumetric variation between said differently temperatured volumes of the working fluid; a primary fluid loop in which the heating/cooling source is fluidly connected between the supply and return chambers of the split buffer to receive said working fluid from the return chamber and heat/cool said working fluid, before loading thereof into the supply chamber of the split buffer; a secondary fluid loop in which at least one heating/cooling unit (FC1, FC2, FC3, HP, MUA, DHW) is fluidly connected between the supply and return chambers of the split buffer to receive said working fluid from the supply chamber and use said working fluid to address a heating/cooling load, before returning said working fluid to the return chamber;
- during circulation of the working fluid through the secondary fluid loop, performing the following steps: (a) monitoring a fluid return temperature (TSWR) of the working fluid in the secondary fluid loop at a location downstream of the at least one heating/cooling unit and upstream of the return chamber of the split buffer; (b) determining whether the fluid return temperature fulfills a targeted minimum temperature differential (ΔT) relative to an output temperature setpoint (TSP) of the heating/cooling source to achieve operating efficiency thereof in an optimal range; (c) when the fluid return temperature (TSWR) fulfills said targeted minimum temperature differential (ΔT), returning the working fluid to the return chamber of the split buffer; and (d) when the fluid return temperature does not fulfill said targeted minimum temperature differential (ΔT), recirculating the working fluid back through the secondary loop.
13. The method of claim 12 wherein said heat/cooling source is a heating source (B1-B2), step (b) comprises determining whether the fluid return temperature fulfills the targeted temperature differential by checking whether the fluid return temperature is less than a control valve setpoint value, step (c) comprises returning the working fluid to the return chamber of the split buffer when the fluid return temperature is less than the control valve setpoint value, and step (d) comprises recirculating the working fluid back through the secondary loop when the fluid return temperature is greater than the control valve setpoint value.
14. The method of claim 12 wherein said heat/cooling source is a cooling source (CH), step (b) comprises determining whether the value of the fluid return temperature fulfills the targeted temperature differential by checking whether the fluid return temperature is greater than a control valve setpoint value, step (c) comprises returning the working fluid to the return chamber of the split buffer when the fluid return temperature is greater than the control valve setpoint value, and step (d) comprises recirculating the working fluid back through the secondary loop when the fluid return temperature is less than the control valve setpoint value.
15. The method of claim 12 wherein comprising, over time, variably adjusting the targeted minimum temperature differential.
16. The method of claim 15 comprising, over time, variably adjusting the targeted minimum temperature differential based at least partly on an outdoor temperature.
17. The method of claim 13 comprising, over time, variably adjusting the control valve setpoint value.
18. The method of claim 17 comprising, over time, variably adjusting the control valve setpoint value based at least partly on an outdoor temperature.
19. The method of claim 12 wherein the secondary fluid loop comprises a plurality of fluid circuits through which the working fluid is respectively delivered to a plurality of different heating/cooling equipment types (HP, MUA, DHW), and the method comprises returning or recirculating working fluid from each of said fluid circuits based on a respective fluid return temperature measured therein.
20. A split buffer tank (SBT) for storing temperature-distinct volumes of working fluid therein as a buffer between primary and secondary fluid loops of a hydronic heating/cooling system, said split buffer tank comprising:
- a vessel (1) having first and second ends that are spaced apart from one another in an axial direction of the vessel, and that are situated oppositely of one another across an interior space of the vessel delimited between said first and second ends, and a circumferential wall that spans axially between the first and second ends of the vessel and closes circumferentially around the interior space thereof;
- a separation disk (2) that is contained in said vessel and divides the interior space thereof into separate supply and return chambers (SC, RC) on opposing sides of said separation disk for respective holding of differently temperatured volumes of the working fluid in isolated fashion from another within said separate supply and return chambers, said separation disk (2) being movable back and forth in the axial direction of the vessel to vary the relative sizes of said supply and return chambers and thereby accommodate volumetric variation between said differently temperatured volumes of the working fluid;
- a shaft spanning across the interior space of the vessel in the axial direction thereof, said shaft penetrating through the first and second ends of the vessel and also through the separation disk, which is slidably disposed around said shaft for sliding movement back and forth along the shaft;
- a supply chamber inlet installed on the first end of the vessel to receive the working fluid from one or more heating/cooling sources in a primary loop of the hydronic heating/cooling system, said supply chamber inlet opening into the supply chamber of the vessel and also receiving a first end portion of the shaft that penetrates through the first end of the vessel, thereby externally supporting said first end portion of the shaft outside the vessel;
- a return chamber inlet installed on the second end of the vessel to receive the working fluid back from a secondary loop of the hydronic heating/cooling system, said return chamber inlet opening into the return chamber of the vessel and also receiving a second end portion of the shaft that penetrates through the second end of the vessel, thereby externally supporting said second end portion of the shaft outside the vessel;
- a supply chamber outlet on the circumferential wall at a location situated axially near the first end to enable supply of the working fluid from the supply chamber into the secondary loop; and
- a return chamber outlet on the circumferential wall at a location situated axially near the second end to enable output of the working fluid from the return chamber into the primary loop.
Type: Application
Filed: Jan 21, 2022
Publication Date: Aug 11, 2022
Inventor: Denering Berrio (Calgary)
Application Number: 17/581,355